GTYQ-TCB6 Gas Detection Alarm Instrument

GTYQ-TCB6 Gas Detection Alarm Instrument

Specify fixed gas monitoring around the target gas and control interface at each point.

  • Select the sensor

    Choose the gas and range required at the installation location.

  • See local status

    The display and configurable alarm levels make readings visible at the detector.

  • Connect plant controls

    Confirm the output and power option compatible with the existing system.

Outputs, power modes and approvals depend on the selected GTYQ-TCB6 configuration.

Overview

The TCB6 series fixed gas detection alarm is a cutting-edge instrument developed by our company. Featuring high-performance gas sensors and microcontroller technology, it combines advanced SMD manufacturing techniques to deliver exceptional repeatability, precise temperature and humidity control, extended service life, and user-friendly operation. This product is designed for gas concentration and leakage detection.

The detector converts air gas concentration signals into digital displays, supporting three output methods: 4-20 mA current signal, RS485 four-wire bus, or M-BUS two-wire bus. It features long transmission distance and excellent interference resistance. The detector is designed for gas safety monitoring and alarm control in environments containing flammable gases, including gas pipelines, municipal utility tunnels, research institutions, hospitals, and schools. It is suitable for hazardous areas with explosive flammable gases (Class II A to II C) and temperature groups from T1 to T6.

Key Features

Gas Sensing & Local Warnings

  • Customizable Alarm Setpoints
  • On-Site Calibration
  • Fast response speed
  • Diffusion detection
  • Compatible with audible & visual alarm lamp
  • Wide Gas Selection
  • High Sensitivity & Stable Reliability
  • Flameproof Design

Control-System Signals & Connections

  • 1-Channel Switch Quantity Output
  • Optional 4-Bus Signal or 4-20mA Signal;Optional LCD Display

Installation, Power & Service

  • Infrared Remote Control
  • IP66 protection grade
  • NB-IoT monitoring
  • DC24V/AC220V power supply
  • Digital Display
  • OEM & ODM & OBM:

Technical Specifications

Applicable gas  combustible, toxic hazardous gas, O₂ etc.
Sampling method  natural diffusion sampling
Detection principle  catalytic bead, electrochemical, infrared, laser, semiconductor etc.
Measuring range  0~100%LEL (combustible); 0~100ppm (toxic), (according to gas type)
Low alarm setpoint  20%LEL (combustible gas)
High alarm setpoint  50%LEL (combustible gas)
Display method  LED digital display
Accuracy  ±3%FS (combustible), (according to gas type)
Operating voltage  DC24V/DC36V/AC220V±15% (subject to order specification and nameplate)
Relative humidity  20~93%RH, non-condensing
Ambient temperature  -40℃~+70℃(Ex); -25℃~+55℃ (toxic)
Power consumption  ≤3W
Ambient pressure  86~106kPa
Response time T₉₀  ≤30s (combustible)
Ex certificate No.  CE21.0719X
Ex mark  Ex db IIC T6 Gb / Ex tb IIIC T80℃ Db
Protection grade  IP66
Connection cable  RVVP 3×1.5mm²; RVVP 4×1.5mm²; RVVP 2×1.5mm²
Transmission distance  ≤1000m
Product weight  ≤1000g
Product dimension  168×155×65 mm