TCB2-F Point Type Four Gas Detector

TCB2-F Point Type Four Gas Detector

Monitor a selected gas combination at a fixed point with local warnings and control-system outputs.

  • Fit the site's gas risk

    The listed sensor and range options let the buyer specify the gases to monitor at the fixed location.

  • Warn before a reading is missed

    Local display, adjustable low/high alarms and sound/light indication support on-site awareness.

  • Connect and service the detector

    The listed relay and RS485 outputs, self-diagnosis and calibration functions support integration and upkeep.

IP66 protection class. Confirm gas combination, sampling version, alarm thresholds and output protocol.

Overview

TCB2-F fixed Gas Detector is a multifunctional intelligent gas detection instrument, the instrument adopts high performance detection devices and micro computer control technology, and combined with automatic mount of advanced manufacturing technology, the products of both the scene buzzing indicating sound and flashing lights , and the real-time display of monitoring gas concentration field. TCB2-F multi-functional gas detector can be in the air gas concentration signal into the electrical signal display and remote transmission, using three wire 4 to 20mA or four RS485 bus output, with long transmission distance and anti-jamming etc.. TCB2-F fixed Gas Detector can be used in chemical plant, smelting, fire, gas refrigeration and papermaking wastewater treatment, food, rubber, pharmaceuticals, petroleum refining, casting, mining, communications and other municipal fire power to anti explosion, poisoning prevention, anti suffocation in the industrial environment. this model candetect 1-4 different gases。

Key Features

Gas Sensing & Sampling

  • Supports detection of flammable and toxic gases
  • High-sensitivity sensor with fast response and excellent stability
  • Reliable detection, intelligent monitoring, and industrial-grade safety—your trusted gas detection solution.
  • Optional 1 to 4-Gas Detection
  • Wide Gas Selection
  • High Sensitivity & Stable Reliability

Local Warnings & Diagnostics

  • Dual-level alarm (low/high) for early risk warning
  • Sound and light alarm indication
  • Sensor fault self-diagnosis with alert notification
  • Integrated Audible & Visual Alarm

Signals & Integration

  • Relay output for external control systems
  • RS485 digital output
  • Compatible with PLC / DCS systems for remote monitoring

Operation & Calibration

  • LCD/LED display for real-time gas concentration and status
  • Infrared Remote Control
  • Intuitive interface for easy operation and monitoring
  • Automatic temperature compensation for improved accuracy
  • Auto zero calibration for stable long-term performance

Installation & Protection

  • Flameproof Design
  • Suitable for harsh industrial environments
  • Explosion-proof structure suitable for hazardous zones
  • Durable construction for continuous industrial use
  • IP66 Waterproof & Dustproof
  • Dual-Chamber Design
  • Optional Stainless Steel Housing

Service & Options

  • OEM & ODM & OBM

Technical Specifications

Applicable gas  Ex, toxic hazardous gas, O2 etc.
Detection principle  catalytic bead, electrochemical, infrared, laser, semiconductor etc.
Sampling method  natural diffusion / pump suction
Display method  LCD display / digital display
Operating voltage  DC24V/DC36V/AC220V±15% (subject to order specification and nameplate)
Alarm  audible & visual alarm
Response time T90  ≤30s (combustible), according to gas type
Ambient temperature  -40℃~+70℃ (combustible); -25℃~+55℃ (toxic)
Relative humidity  20~93%RH, non-condensing
Ex mark  Ex db IIC T6 Gb / Ex tb IIIC T80℃ Db
Ex certificate No.  CCRI25.1414X
Protection grade  IP66
Metrology approval No.  2018C241-41
Connection cable  RVVP 4×1.5mm²
Transmission distance  ≤1000m
Weight  2500g
Other functions  optional combination of four kinds of gases
Product dimension  212×195×80 mm

Videos

Available Gases & Detection Ranges

The gases and ranges below are configuration options. TCB2-F Point Type Four Gas Detector; confirm the final sensor combination and ranges with our team.

Common Gas Parameter listing
Gas detected Measuring Range Optional Range Resolution Rat Response Time
LEL -combustible gas 0-100%LEL 0-100%VOL (Infrared or catalytic ) 1%LEL/1%vol ≤10s
carbon monoxide 0-1000PPm 0-500/2000/5000PPm 0.1/1PPm ≤10s
TVOC 0-100PPM 0-100PPM 0.1PPm/1PPM ≤15s
hydrogen 0-100%LEL 0-1000PPM 1%LEL/1PPM ≤15s
natural gas 0-100%LEL 0-100%LEL 1%LEL ≤10s
Oxygen-O2 0-30%VOL 0-30%、0-100%VOL 0.1%vol ≤10s
ozone 0-10PPm 0-20、100PPm 0.01PPm/0.1PPM ≤15s
hydrogen sulfide-H2S 0-100PPm 0-50、200、1000PPm 1/0.1PPm ≤10s
Methane-CH4 0-100%LEL 0-100%VOL 1%LEL/1%vol ≤10s
fluorine 0-10PM 0-1、10PPM 1/0.1PPm ≤15s
hydrogen chloride 0-20PPm 0-20/50PPm/100PPM 0.01/0.1PPm ≤15s
Nitrogen-N2 0-30%VOL 0-30%VOL、100%VOL 0.1%LEL/1PPM ≤10s
hydrogen 0-100%LEL 0-1000PPm 1%LEL/0.1PPm ≤15s
chlorine 0-20PPm 0-10、100PPm 0.1PPm ≤15s
ammonia gas 0-100PPm 0-50、500、1000PPm 1/0.1PPm ≤15s
oxynitride 0-20PPm 0-50、1000PPm 0.1/1PPm ≤15s
methanal 0-20PPm 0-50、100PPm 1/0.1PPm ≤15s
sulfur dioxide 0-20PPm 0-50、1000PPm 0.1/1PPm ≤15s
nitric oxide 0-250PPm 0-500、1000PPm 1PPm ≤15s
nitrogen oxide 0-20PPm 0-50、1000PPm 0.1/1PPm ≤15s
phosphine 0-20PPm 0-20、100PPm 0.1PPm ≤15s
acrylonitrile 0-100PPM 0-100PPm 0.1/1PPm ≤15s
carbon dioxide 0-5000PPm 0-1%/5%/10%VOL(Infrared ) 1PPM/0.01%VOL ≤15s
hydrogen fluoride 0-10PPm 0-1、10、50、100PPM 0.01/0.1PPm ≤15s
Xylene/methylbenzene 0-20PPm 0-5、10、50、100PPm 0.01/0.1PPm ≤15s
oxirane 0-100PPm 0-100PPm 1/0.1PPm ≤15s
For other gases and measuring ranges, please contact us directly!
Note: Not all gases and range are listed, if you need more information, please contact us.

Request a Quote

Tell us the target gas, measuring range, application and quantity. Confirm gas combination, sampling version, alarm thresholds and output protocol.

    User Type: