S600Ex-IR2-UV Dual-Spectrum Flame Detector

S600Ex-IR2-UV Dual-Spectrum Flame Detector

Combine two infrared bands with ultraviolet sensing for fixed-point flame monitoring.

  • Assess multiple optical signals

    The IR and UV sensors help distinguish a flame event from some background light and heat sources.

  • Monitor the hazard area

    Plan detector positions around the expected fuel, sightlines and possible obstructions.

  • Link to the alarm system

    Relay contact and RS-485 outputs support connection to a compatible control panel.

Confirm the expected fire type, mounting position and site interference sources before selecting the final configuration.

Overview

S600-ExIR2-UV point type infrared / UV flame detector contains two infrared wavelength sensors and a highly sensitive imported UV/ultraviolet sensor and optical filter. The ultraviolet sensor can respond to ultraviolet radiation at the moment of fire and explosive ignition. The other two infrared sensors, one has the highest sensitivity to the CO2 emission spectrum (4.4μm), and the other interferes with ambient light and heat radiation For detection, the detector makes a composite judgment on the ultraviolet and infrared signals generated in the event of a fire, and performs multi-signal processing in conjunction with the logical comprehensive judgment of the flame flicker frequency to minimize false alarms and the best fire detection performance required. The flame detector has an early warning function for the fire of organic materials such as hydrocarbons and the fire of inorganic materials.

We provide flame  detector OEM/ODM service.

Key Features

Explosion-Proof CertificationSound And Light Alarm

Responsive

Certificate Is Complete

Four To Adjust

Quality Assurance

Technical Specifications

Response spectral range

4.4μm, 3.8μm, 185-260nm

Response time

6s

Viewing angle range

≤110 °

Detection distance

Class I

Ambient temperature

-10 ~ 55 ℃

Environmental humidity

≤95% RH

Pressure range

86 ~ 106Kpa

Working voltage

DC24V

Working current

current≤25mA, alarm current≤35mA

Executive standard

GB15631-2008, GB12791-2006

Explosion-proof grade

EX d ⅡC T6 Gb

Protection grade

IP66

Signal output

Switching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)

Installation method

wall or ceiling

Cable outlet thread

20mmX1.5mm free conversion G1 / 2 optional

Dimensions

(190X160X110) mm

Shell material

die-cast aluminum

Weight

1Kg

Advantages

dustproof, explosion-proof, corrosion-proof

Request a Quote