JB-TB-GDB18 Gas Alarm Controller

JB-TB-GDB18 Gas Alarm Controller

Monitor multiple gas-detector points and make their alarms and control signals easier to manage together.

  • Bring mixed detector wiring together

    The listed 4–20 mA, four-bus and two-bus interfaces offer connection choices for the planned field network.

  • Respond to the right point

    Configurable gas names and alarm thresholds, local indication and relay outputs support a site-specific response.

  • Investigate system status

    The controller's signal processing, fault detection and online zero correction support operator review and maintenance.

Share detector count, signal types, outputs and alarm logic for configuration review.

Overview

The JB-TB-GDB18 gas alarm controller is a multi-point monitoring gas alarm controller developed by our company. It is used to detect the concentration of target gases in the ambient air, capable of integrating multiple detectors for different gas components and simultaneously monitoring multiple points. This product also features both split-wire and bus interfaces, meeting the needs of various wiring configurations for the detectors. This system uses a microprocessor as the control unit and high-precision sensors as detection components, offering high sensitivity and fast response. When the concentration of the target gas detected in the environment reaches or exceeds the warning threshold, the controller immediately triggers an audio-visual alarm to alert us to take timely safety measures. It also activates the control unit to manage the exhaust ventilation or other peripheral devices, preventing poisoning incidents, explosions, and fires, thus ensuring the safety of lives and property. The design, manufacture and verification of this product comply with the following national standards: GB 12358—2024 General technical requirements for environmental gas detection and alarm instrument in workplaces

Key Features

Alarm Settings & Response

  • Customizable Alarm Setpoints
  • Customizable Gas Names
  • Built-In Audible & Visual Alarm

Detector Inputs, Outputs & Records

  • 4-Channel 4-20mA Interface, 1-Loop 4-Bus Interface & 1-Loop 2-Bus Interface
  • The product is embedded with a microprocessor and rich software functions to complete signal sampling of transmitter, real-time data calculation, system fault detection, power management, alarm display, alarm peripheral drive and other functions
  • Multi-channel passive relay contact output
  • 2-Channel Switch Quantity Output
  • Alarm & Fault Record Storage
  • Optional 4G Cloud Upload

Operator Controls & Power

  • Customizable Device Time
  • LCD Chinese display, simple and clear
  • Intelligent system: convenient online zero correction
  • The installation is simple. Fix the bracket on the wall and hang the controller to complete the installation
  • Password Management
  • Button Operation
  • Manual Reset & Mute
  • Automatic Main/Backup Power Switching
  • OEM & ODM & OBM

Technical Specifications

Installation method  Indoor wall-mounted
Response time  ≤30s
Indication method  LCD display, sound and light alarm
Working environment temperature  -10℃~+50℃
Working environment humidity  ≤93%RH
Main power supply  AC220V+15%, 50Hz+1%
No-load power  ≤10W
Detector power supply voltage  DC24V±10%
Backup power undervoltage alarm value  DC21V±1V
Dimensions  L295 mmxW226 mmxH86 mm
Product weight  about 3.95kg
Cable requirements  2RVVP4x1.5mm2 (four-bus),≥RVVP 3×1.5mm2 (three-wire),≥RVVP 2×1.5mm2 (two buses)
Communication distance between detector and host  ≤1000m
Number of channels of this machine 4 buses: 1 channel: 3 lines: 12 channels:2 buses: 2 channels;
Control output contacts 2 groups of passive switches: 1 group of 24V pulse signals:1 group of AC220V pulse signals
Output signal  RS485, (4~20)mA.
Point-type combustible gas detector with two bus signals