S600-ExIR1-UV point type infrared ultraviolet flame detector

S600-ExIR1-UV point type infrared ultraviolet flame detector

Monitor fixed areas for flame events using both infrared and ultraviolet sensing.

  • Check two optical signals

    IR and UV sensors evaluate different radiation from a potential flame event.

  • Plan visible coverage

    Review the expected fuel, clear sightlines and nearby sources of UV or heat before installation.

  • Send an alarm signal

    Relay contact and RS-485 outputs support connection to a compatible fire alarm or control system.

Confirm the fire scenario, mounting location and required interface for the ordered detector.

Overview

S600-ExIR1-UV point type infrared / ultraviolet flame detector includes an infrared wavelength sensor and a highly sensitive imported UV ultraviolet sensor and optical filter. The ultraviolet sensor can respond to ultraviolet radiation at the moment of fire and explosive ignition. The infrared sensor has the highest sensitivity to the CO2 emission spectrum (4.4μm) produced by the combustion of hydrocarbons. The detector is sensitive to ultraviolet rays generated in the event of a fire Composite judgment with infrared signal and multi-signal processing combined with logical comprehensive judgment of flame flicker frequency to minimize false alarm and the best fire detection performance required. The flame detector has an early warning function for the fire of organic materials such as hydrocarbons and the fire of inorganic materials.   We provide flame  detector OEM/ODM service.

Key Features

Explosion-Proof CertificationSound And Light Alarm

Responsive

Certificate Is Complete

Four To Adjust

Quality Assurance

Technical Specifications

Response spectral range

4.4μm, 185-260nm

Response time

6s

Viewing angle range

≤110 °

Detection distance

Class I

Ambient temperature

-10 ~ 55 ℃

Environmental humidity

≤95% RH

Pressure range

86 ~ 106Kpa

Working voltage

DC24V

Working current

current≤25mA, alarm current≤35mA

Executive standard

GB15631-2008, GB12791-2006

Explosion-proof grade

Ex d ⅡC T6 Gb

Protection grade

IP66

Signal output

Switching relay contact output, RS-485 (built-in DIP switch, can set the address of the detector)

Installation method

wall or ceiling

Cable outlet thread

20mmX1.5mm free conversion G1 / 2 optional

Dimensions

(190X160X110) mm

Shell material:

die-cast aluminum

Weight

1Kg

Advantages

dustproof, explosion-proof, corrosion-proof